GSO IEC/TR 61294:2014由GSO 发布于 2014-12-25。
GSO IEC/TR 61294:2014在国际标准分类中归属于: 29.040.10 绝缘油。
GSO IEC/TR 61294:2014 绝缘液 局部放电起始电压的测定 试验程序的最新版本是哪一版?
最新版本是 GSO IEC/TR 61294:2014 。
This technical report describes a test procedure to measure the pa rtial discharge inception voltage (PDIV). It is one of a group of methods which have been recently developed to describe the behaviour of insulating liquids when subjected to high electrical stress. The method is applicable to all types of insulating liquids used in medium and high voltage equipment. Nevertheless the equipment described in this repo rt may not be adapted to liquids with values of PDIV greater than 70 kV (see annex A). Complementary information may be obtained by the gassing properties (IEC 628) and the lightning impulse breakdown voltage (IEC 897) in addition to the widely used measurement of electric strength (IEC 156).
随着电网的迅速发展和输电电压的提高,电网和电力用户对大型电力变压器的绝缘可靠性的要求越来越高。由于局部放电试验对绝缘没有破坏性作用而且十分灵敏,能有效地发现变压器绝缘内部的固有缺陷或运输、安装工程中产生危及安全的缺陷,因而现场局部放电试验得到广泛应用,已列为72.5kV及以上电压等级变压器现场必做的交接试验项目。 局部放电及其原理 局部放电又称静电游离,就是静电荷流动的意思。...
分级绝缘:降低了中点绝缘水平的变压器叫做分级绝缘变压器(即中性点绝缘水平与线端不同) 起始放电电压:当施加于试品上的试验电压从还末在测量仪器上观察到局部放电(放电量刚刚超过局放规定值)的较低电压遂渐上升,到刚好到能观察到局部放电信号时的zui低电压称为局部放电起始放电电压。 ...
预激磁电压是模拟运行中过电压,预激磁电压激发的局部放电量不应由局部放电试验电压所延续,概念是系统上有过电压时所激发的局部放电量不会由长期工作电压所延续。这一方法是使变压器或互感器在Um/√3长期工作电压下无局部放电量,以保证变压器能安全运行,使局部放电起始电压与局部放电熄灭电压都能高于Um/√3。 ...
1.串联谐振试验装置闪络现象 当在气体或液体电介质中沿固体绝缘表面发生破坏性放电现象,称之为闪络。闪络现象是指固体绝缘体周围的气体或液体电介质被击穿时,击穿电压沿固体绝缘子 表面放电的现象。闪络现象其放电时的电压称为闪络电压。绝缘体发生闪络后,电极间的电压迅速下降到零或接近于零,闪络通道中的火花或电弧使绝缘表面局部过 热造成炭化,损坏表面绝缘。 ...