IEC 60987:2007
核电站.对安全性很重要的仪器仪表和控制.基于计算机系统的硬件设计要求

Nuclear power plants - Instrumentation and control important to safety - Hardware design requirements for computer-based systems


标准号
IEC 60987:2007
发布
2007年
中文版
GB/T 41142-2021 (修改采用的中文版本)
发布单位
国际电工委员会
替代标准
IEC 60987:2013
当前最新
IEC 60987:2021
 
 
引用标准
IAEA 50-C/SG-Q-1996 IAEA NS-G 1.3 IEC 60780 IEC 60812 IEC 60880 IEC 61000 IEC 61025 IEC 61513:2001 IEC 62138 ISO 9001
被代替标准
IEC 45A/662/FDIS:2007 IEC 60987:1989
适用范围
1.1 General This International Standard is applicable to NPP computer-system hardware for systems of Class 1 and 2 (as defined by IEC 61513). The structure of this standard has not changed significantly from the original 1989 issue; however, some issues are now covered by standards which have been issued in the interim (for example, IEC 61513 for system architecture design) and references to new standards have been provided where applicable. The text of the standard has also been modified to reflect developments in computer system hardware design, the use of pre-developed (for example, COTS) hardware and changes in terminology. Computer hardware facilities used for software loading and checking are not considered to form an intrinsic part of a system important to safety and, as such, are outside the scope of this standard. NOTE 1 Class 3 computer-system hardware is not addressed by this standard, and it is recommended that such systems should be developed to commercial grade standards. NOTE 2 In 2006 the development of a new standard to address hardware requirements for “very complex” hardware was discussed within IEC SC 45A. If such a standard is developed then that standard would be used for the development of “very complex” hardware in preference to IEC 60987. 1.2 Use of this standard for pre-developed (for example, COTS) hardware assessment Although the primary aim of this standard is to address aspects of new hardware development, the processes defined within this standard may also be used to guide the assessment and use of pre-developed hardware, such as COTS hardware. Guidance has been provided in the text concerning the interpretation of the requirements of this standard when used for the assessment of such components. In particular, the quality assurance requirements of 4.3, concerning configuration control, apply. Pre-developed components may contain firmware (as defined in 3.8), and, where firmware software is deeply imbedded, and effectively “transparent” to the user, then IEC 60987 should be used to guide the assessment process for such components. An example of where this approach is considered appropriate is in the assessment of modern processors which contain a microcode. Such a code is generally an integral part of the “hardware”, and it is therefore appropriate for the processor (including the microcode) to be assessed as an integrated hardware component using this standard. Software which is not firmware, as described above, should be developed or assessed according to the requirements of the relevant software standard (for example, IEC 60880 for Class 1 systems and IEC 62138 for Class 2 systems). 1.3 Applicability of this standard to programmable logic devices development I&C components may include programmable logic devices that are given their specific application logic design by the designer of the I&C component, as opposed to the chip manufacturer. Examples of such devices include complex programmable logic devices (CPLD) and field programmable gate arrays (FPGA). While the programmable nature of these devices gives the development processes used for these devices, some of the characteristics of a software development process and the design processes used for such devices, are very similar to those used to design logic circuits implemented with discrete gates and integrated circuit packages. Therefore, the design processes and design verification applied to programmable logic devices should comply with the relevant requirements of this standard (i.e. taking into account the particular features of the design processes of such devices). To the extent that software-based tools are used to support the design processes for programmable logic devices, those software tools should generally follow the guidance provided for software-based development tools in the appropriate software standard, i.e. IEC 60880 (Class 1 systems) or IEC 62138 (Class 2 systems).

IEC 60987:2007相似标准


推荐

核岛控制系统特点研究

核岛仪控系统设计必须遵从以下原则:   1)根据电厂安全性目标设计,满足电厂纵深防御要求。正常运行时,当出现异常工况,由电厂控制系统进行调节来使电厂恢复正常运行;当发生预期设计瞬态事件时,由保护系统来触发执行安全功能;设计基准事故时,由保护系统来触发执行安全功能。   2)安全重要仪控系统采用冗余设计,满足单一故障准则。...

AVR单片机入门一:单片机嵌入式系统结构与应用

所以单片嵌入系统软程序发与应用程序开发还是有很大不同,单片嵌入系统程序开发要求开发者系统硬件电路有清晰了解,一个不了解硬件电路程序员是无法做好嵌入式系统程序开发。实际上在大多数时候单片嵌入式系统硬件开发与软件开发是不区分,一个嵌入式系统开发人员通常软件与硬件都有很深了解。  ...

智能仪器基本组成原理及其发展趋势分析

4.4融合ispemit技术,实现仪器仪表系统internet接入(网络化)   伴随着网络技术飞速发展,internet技术正在逐渐向工业控制智能仪器仪表系统设计领域渗透,实现智能仪器仪表系统基于internet通讯能力以及设计智能仪器仪表系统进行远程升级、功能重置系统维护。   ...

仪器仪表设计现代化智能化研究

国外大仪器计算机制造厂家,无一例外都配备有高水平自动检测、自动校准和在线维修技术功能系统。  六、完善配套服务设施  智能仪表都配有详细使用说明,给出许多实用操作使用程序,并附有各种可选择、用于扩大应用范围附件。这些附件设计都要同主机设计进行一体化考虑,仪表易损件定期更换件都配套供应,使用户感到十分方便。这种“软科学”发展了,仪器仪表硬件电路智能化水平就能迅速提高。...


谁引用了IEC 60987:2007 更多引用





Copyright ©2007-2022 ANTPEDIA, All Rights Reserved
京ICP备07018254号 京公网安备1101085018 电信与信息服务业务经营许可证:京ICP证110310号