Radio interference characteristics of overhead power lines and high-voltage equipment - Part 2: Methods of measurement and procedure for determining limits
This part of CISPR 18, which is a technical report, applies to radio noise from overhead power
lines and high-voltage equipment which may cause interference to radio reception.
The frequency range covered is 0,15 MHz to 300 MHz.
A general procedure for establishing the limits of the radio noise field from the power lines
and equipment is recommended, together with typical values as examples, and methods of
measurement.
The clause on limits concentrates on the low frequency and medium frequency bands and it is
only in these bands where ample evidence, based on established practice, is available. No
examples of limits to protect radio reception in the frequency band 30 MHz to 300 MHz have
been given, as measuring methods and certain other aspects of the problems in this band
have not yet been fully resolved. Site measurements and service experience have shown that
levels of noise from power lines at frequencies higher than 300 MHz are so low that
interference is unlikely to be caused to television reception.
The values of limits given as examples are calculated to provide a reasonable degree of
protection to the reception of broadcasting at the boundary of the recognized service areas of
the appropriate transmitters in the radio frequency bands used for a.m. broadcasting, in the
least favourable conditions likely to be generally encountered. These limits are intended to
provide guidance at the planning stage of the line and national standards or other
specifications against which the performance of the line may be checked after construction
and during its useful life.
The measuring apparatus and methods used for checking compliance with limits should
comply with the respective CISPR specifications, as e.g. the basic standards series CISPR 16,
see [1]*.
2 Normative references
The following referenced documents are indispensable for the application of this document.
For dated references, only the edition cited applies. For undated references, the latest edition
of the referenced document (including any amendments) applies.
IEC 60050-161, International Electrotechnical Vocabulary (IEV) – Chapter 161:
Electromagnetic compatibility
IEC 60060-2, High-voltage test techniques – Part 2: Measuring systems